An electrical impedance relay, also known as a percentage differential relay or a high impedance differential relay, is used in transformer differential protection schemes to detect and protect against internal faults within the transformer windings. It operates based on the principle of comparing the currents entering and leaving the transformer to determine if there is an abnormal condition.
Here's how an electrical impedance relay operates in transformer differential protection:
Current Comparison: The relay continuously measures the currents entering and leaving the transformer. Typically, current transformers (CTs) are used to step down the currents to a level suitable for the relay's operation.
Current Balance: Under normal operating conditions, the currents entering and leaving the transformer should be equal (balanced), as the total current flowing into the transformer must be equal to the total current flowing out. This is because the transformer operates on the principle of conservation of energy, and any imbalance indicates an abnormality.
Differential Operation: The electrical impedance relay calculates the difference (differential current) between the currents entering and leaving the transformer. This is done by taking the absolute value of the algebraic difference between the currents.
Setting the Threshold: The relay is typically set with a predefined percentage differential threshold. The percentage is based on the transformer's characteristics and the operating conditions. For example, if the relay is set to 10%, it means that the relay will trip if the differential current exceeds 10% of the rated current of the transformer.
Operation Condition: Under normal conditions, the differential current should be very close to zero, well below the set threshold. The relay constantly monitors the differential current and compares it to the set threshold.
Fault Detection and Tripping: If there is an internal fault within the transformer (such as a short circuit or winding failure), it will cause an imbalance in the currents. As a result, the differential current will exceed the set threshold. When the differential current exceeds the threshold, the relay will detect this condition as a fault and issue a tripping signal to the associated circuit breaker.
Circuit Breaker Tripping: The tripping signal sent by the impedance relay causes the circuit breaker to open, isolating the faulty transformer from the rest of the power system. This action prevents further damage to the transformer and helps protect the overall power system from potential cascading failures.
Overall, the electrical impedance relay provides sensitive and selective protection for transformers, quickly detecting internal faults and minimizing their impact on the system. It is an essential component of modern transformer differential protection schemes in power systems.