Differential protection is a fundamental and widely used technique in power systems to ensure the reliable and selective protection of transformers. Transformers are crucial components in power systems, responsible for changing voltage levels and facilitating efficient power transmission and distribution. Differential protection aims to rapidly detect and isolate faults occurring within the transformer, safeguarding it from potential damage and minimizing disruption to the power system.
The basic idea behind differential protection is to compare the currents entering and leaving the transformer. In a healthy operating condition, the current entering the transformer (primary side) should be equal to the current leaving the transformer (secondary side), considering losses. This principle is derived from Kirchhoff's current law, which states that the total current entering a junction should equal the total current leaving it.
Here's how differential protection for transformers works:
Current Transformers (CTs): Current transformers are installed on both the primary and secondary sides of the transformer. These CTs step down the high currents on the primary side to a proportional and measurable value suitable for protection and measurement devices.
Current Comparison: The current signals from the CTs are then fed into a differential protection relay or a numerical relay. This relay constantly calculates the difference between the currents entering and leaving the transformer.
Setting Criteria: Differential protection relays are configured with settings that establish the allowable "operating margin" or "restraint" to account for normal operational disparities (such as magnetizing currents and tap changer effects) between the two currents. These settings are based on the transformer's characteristics and design.
Operation Principle: Under normal conditions, when the transformer is operating without any internal fault, the currents entering and leaving the transformer should be nearly equal, and the differential protection relay remains in a "rest" or "balanced" state.
Fault Detection: In the event of an internal fault within the transformer (such as a winding short circuit), the faulted winding's current will differ significantly from the other winding's current. This difference will exceed the set operating margin of the protection relay, causing it to operate.
Operation Response: When the differential protection relay detects a fault based on the current imbalance exceeding the set threshold, it initiates a trip signal to the circuit breaker connected to the transformer. The circuit breaker promptly opens, isolating the faulty transformer from the power system.
Selectivity and Speed: Differential protection is highly selective, meaning it only trips the specific circuit breaker connected to the faulted transformer, minimizing system disruption. The speed of operation is also a significant advantage, as rapid fault detection and isolation prevent further damage and reduce downtime.
Communication and Backup Protection: Modern differential relays can also communicate with other protection devices and the overall control system. Backup protection schemes can be implemented to provide an additional layer of protection in case the differential protection fails to operate properly.
In summary, differential protection for transformers relies on comparing the currents entering and leaving the transformer to rapidly detect internal faults and isolate the faulty transformer from the power system. This technique is essential for maintaining the reliability and stability of power systems.