A three-phase transformer differential protection scheme is designed to protect power transformers from internal faults that can cause significant damage or disruption to the power system. This protection scheme ensures that any imbalance in the currents entering and leaving the transformer is detected and properly acted upon.
Here's how a basic three-phase transformer differential protection scheme works:
Current Transformers (CTs) Installation: Current transformers are installed on the primary and secondary sides of the transformer. These CTs step down the currents to a level suitable for measurement and protection purposes. The primary side CTs measure the currents entering the transformer, while the secondary side CTs measure the currents leaving the transformer.
Current Comparison: The currents measured by the CTs on both the primary and secondary sides are compared. In a healthy operating condition, the sum of the currents entering the transformer (primary side) should be equal to the sum of the currents leaving the transformer (secondary side). This is due to the principle of conservation of energy.
Differential Relay: A differential relay is connected to the CTs and continuously monitors the currents. The relay calculates the difference between the currents entering and leaving the transformer. If the difference exceeds a pre-set threshold, known as the "restraint" current, the relay will initiate a trip signal.
Operating Characteristic: To avoid unnecessary tripping due to inrush currents during transformer energization, the differential relay is designed with a specific operating characteristic. This characteristic includes a restraint characteristic, which ensures that the relay only trips when an actual fault occurs, and not during normal transient conditions.
Harmonic Restraint: The relay may also include harmonic restraint features to further enhance the selectivity and accuracy of the protection scheme. Harmonic restraint ensures that the relay doesn't respond to harmonics present in the currents, which could cause false tripping.
Buchholz Relay: In addition to the differential protection scheme, a transformer may also be equipped with a Buchholz relay, which detects gas accumulation (usually caused by internal faults) within the transformer oil. The Buchholz relay can provide an additional level of protection and helps to identify the severity of the fault.
Alarm and Trip Signals: When the differential relay detects a fault, it sends a trip signal to the circuit breaker connected to the transformer. The circuit breaker then opens, disconnecting the transformer from the power system. Additionally, an alarm signal may be generated to alert operators of the fault, allowing them to take appropriate actions.
It's important to note that modern transformer differential protection schemes can be more sophisticated and incorporate advanced features, such as adaptive settings, communication capabilities, and integration with overall power system protection schemes. These features enhance the reliability and performance of transformer protection in complex power networks.